The case study describes the design, testing, and construction of rotary-driven pipe piles for an 8-to-9-story commercial building on Manhattan’s Upper East Side. The congested site has variable soils, including uncontrolled fill and compressible former marsh deposits, and is bordered by older buildings on shallow foundations that were vulnerable to vibration and settlement.<br /><br />The project team selected closed-ended, 12.75-inch-diameter steel pipe piles with sacrificial helical tips. Installed by rotation and downward force rather than impact driving, the piles displace soil without producing drill spoils. Each was designed for 75 tons of net compression capacity and extended approximately 110 feet below cutoff. Because rotary-driven piles were not a prescribed type in the 2014 New York City Building Code, the project required specific approval from the Department of Buildings.<br /><br />An 11-pile test program included static compression, uplift, and lateral load tests, as well as repeated torque measurements to investigate capacity gain from soil setup. The load tests met code acceptance requirements, although observed settlement differed substantially between the two compression-test piles. Re-torque results did not establish a clear trend in capacity increase over time. The tests informed repeatable production installation criteria based on rotational frequency, rotary and crowd pressures, and minimum embedment.<br /><br />A total of 320 production piles were installed, some as close as 2 feet to neighboring buildings. Monitoring generally showed that adjacent-building movements and vibrations remained within project limits. Installation was fast and clean, though long pile sections and welded splices affected production; an approved change in weld detail reduced splice time.<br /><br />The project demonstrated that rotary-driven pipe piles can provide a cost-effective foundation solution for constrained urban sites while limiting disturbance. The authors recommend direct torque measurement during installation and emphasize that differential pile settlement should be anticipated in design.
Keywords
rotary-driven pipe piles
Manhattan Upper East Side
commercial building foundation
vibration-sensitive urban site
steel pipe piles
static load testing
soil setup
Department of Buildings approval
compressible marsh deposits
production pile installation
×
Please select your language
1
English