Effects of Atmospheric Conditions on Energy Pile Performance
Availability
On-Demand
Cost
$0.00
Credit Offered
No Credit Offered

This study focuses on quantifying the effects of water infiltration on a full-scale energy pile system’s ability to meet the thermal demand of an HVAC system. Theoretically, an energy pile system should increase its thermal capacity after a rain event due to increased moisture content creating an increase in thermal conductivity of the surrounding soil matrix. The United States Air Force Academy has an energy pile research site consisting of 8 full-scale energy piles located below a shower facility. The local colluvium surrounding the piles allows for relatively high water infiltration during rain events. This study uses an 11kW Precision Geothermal Geocube to apply a thermal load on two single-loop piles. A weather station located south of the structure records atmospheric conditions. Results indicate that moderate rain events can caused up to a 23% increase in the system’s thermal exchange capacity. This change is due to the increase in moisture content near the surface, which penetrates to deeper soil layers with time. The time required for moisture to penetrate to greater depths and then dissipate in the soil matrix, explains why increased system performance is seen for over a week following the passing of a singular rain event.

Subjects: energy piles, ground source heat exchange, thermally active geotechnical systems

Author: Randall A. Pietersen and Melissa S. Beauregard, Ph.D.