High Capacity Hollow Core Bar Piles
Availability
On-Demand
Cost
$0.00
Credit Offered
No Credit Offered

A 17 story building was constructed at the Brooklyn Navy Yard on a site with a long history of development. Most recently the site supported a dewatering well and craneway to service two adjacent drydocks. The subsurface conditions generally consist of the following strata and approximate depths: miscellaneous fill and debris to 20 ft., organic soils to 35 ft., liquefiable sand to 45 ft., varved clay to 65 ft., glacial till to 95 ft. and gneiss bedrock. Hollow core bar piles replaced 18 in. diameter caissons on a 1.67:1 basis. The resulting service loads on the hollow bar piles were 600 kips compression, 21 kips lateral, 180 kips tension and 450 inch-kips moment. The top 30 feet of the hollow bar was cased with a 16 in. x 0.375 in. Grade 50 steel pipe. The piles were socketed 6 feet into bedrock. An extensive load testing program confirmed the axial and lateral load capacities. The paper will also discuss some adjustments to the installation procedure based on the load test program.

Subjects: Driven Pile; Axial Capacity; Construction Problems

Author: Lawrence F. Johnsen, Sr. Consultant, Felix Ferrer, President, Dino Tomasetti Jr., President and Owner and Cassandra A. Wetzel, Associate Principal

Publisher: DFI

Annual Conference Proceedings